About this document
U Value of Solid Brick Wall Analysis by Veeramanikandan Senthilnathan is a document available to read on EtoBox.
This document calculates the total thermal resistance and U-value for a battery room wall consisting of multiple layers. It lists the thickness, density, thermal resistance, and thermal mass of each layer including sand lime brick, air space, sand cement plaster, and wall tiles. The total thermal resistance is calculated as 14.28 sqft-°F-h/Btu and the overall U-value of the wall is calculated as 0.07 Btu/h-ft2-°F.
- Author
- Veeramanikandan Senthilnathan
- Language
- EN