This document provides the design data for the hydraulic fire protection calculation of the Schlumberger OFS Base Dhahran project. It specifies an occupancy classification of light hazards for an area of 1500 square feet. A minimum residual pressure of 20 psi is required at the design flow. The average protection area per sprinkler is 100 square feet based on a 10 foot spacing. A total of 15 sprinklers need to be calculated. The fire hose cabinets have a total design water capacity of 100 gpm.