Rankine Cycle and Refrigeration Analysis by Ralph Segundo Salvador is a document available to read on EtoBox.

This document provides a step-by-step solution to analyzing a two-stage cascade refrigeration system operating between -55°F and 90°F using two different refrigerants. Each refrigeration cycle is analyzed separately on pressure-enthalpy diagrams to determine the heat transfer and work terms. For the first cycle using ammonia between -55°F and 0°F, the cooling rate is determined to be 548.7 Btu/lbm and the refrigerant mass flow rate is calculated as 0.364 lbm/s. The two cycles are connected via a heat exchan