1. A single-phase-to-ground fault between the generator and power transformer was calculated to have a fault current of 0.083 pu or 347 A for a generator system with three 21,875 kVA generators. The generator differential relays would operate for this fault at 12 times pickup. 2. For a generator system with surge capacitors of 0.25 μF, generator-transformer lead capacitance of 0.004 μF, and power transformer capacitance of 0.03 μF, a single-line-to-ground fault would produce a fault current that is calcul