Field Density Test at 765 kV Substation by reeet87 is a document available to read on EtoBox.
The document summarizes the results of field dry density tests conducted on soil samples taken from the construction site of a 765 kV bay extension. Three samples were tested to determine the moisture content, wet density, dry density and degree of compaction. The average degree of compaction achieved was 97.95%, which meets the required compaction of 95%. The tests were conducted according to Indian Standard IS: 2720 by ABB India Ltd. at the 765/400 kV substation site owned by Power Grid Corporation of Ind