The power readings from the motor relay are incorrect because it is calculating power using the primary voltage rather than the secondary 11kV voltage supplied to the motors. [1] Dividing the power reading by 3 or changing the voltage transformer ratio will not solve the issue because the power factor angle is still incorrect. [2] The best solution is to install a voltage transformer on the secondary side to directly measure the 11kV supply voltage. However, this requires additional outdoor construction and