External Hydrant Design per IS 13039:2014 by vipulchakravarty is a document available to read on EtoBox.

What is External Hydrant Design per IS 13039:2014 about?

This document details the design of an external fire hydrant system for a 220-meter tunnel, adhering to IS 13039:2014 standards. The system requires a minimum flow of 2280 L/min, with hydrants spaced at 60-meter intervals, totaling five hydrants. A 200 mm diameter ductile iron pipe is recommended to ensure adequate flow and pressure throughout the system.