CBI Building Illumination Test Report by hazelgayeta.ppgconstcorp is a document available to read on EtoBox.

What is CBI Building Illumination Test Report about?

The document presents the illumination test results for the EW-3488 Rehabilitation of CBI Building, conducted on January 23, 2023. It includes measurements for both indoor and outdoor lighting, comparing designed illumination levels to measured values, with a total average of 421.58 lux for indoor and 41.25 lux for outdoor areas, both passing the required standards. The test was completed by Jenny L. Maderazo, with acceptance by S. Magpantay, representing the client.