Can I read Generator Polarization Index Test Data on EtoBox?
Generator Polarization Index Test Data by andres is a document available to read on EtoBox.
What is Generator Polarization Index Test Data about?
The document details a Generator Polarization Index (PI) test conducted on July 6, 2025, for a Siemens generator at the Central Santa Cruz substation. It includes generator specifications, test conditions, and polarization index readings over a 10-minute period. The results indicate polarization index values of 1.16, 1.29, and 1.15 for the three phases U, V, and W respectively.