Genset Sizing for Semberah Field by Himawan Sigit Nugroho is a document available to read on EtoBox.

This document provides genset sizing calculations for four surface production facilities in the Semberah Field: Semberah Station, Sambutan Station, Binangat Junction, and Tanjung Batu Metering Station. It calculates the minimum gas engine and diesel engine genset capacities required at each facility based on the normal continuous load, largest motor starting load, and a momentary excess factor of 1.5 pu for 15 seconds. The calculations determine the genset sizes needed range from 85.69 kVA to 87.06 kVA. Att