Can I read Fire Water Demand Calculation for SMGP on EtoBox?

Fire Water Demand Calculation for SMGP by chy_id is a document available to read on EtoBox.

What is Fire Water Demand Calculation for SMGP about?

This document calculates the fire water demand for the Sorik Marapi Geothermal Plant. It specifies that each outdoor hydrant must supply 250 gpm within a 50 meter radius, with hydrants no more than 76 meters apart. The largest predicted fire scenario will be used to design the fire water pump, nozzles, and pond, which must supply water for 4 hours. The fire water demand for the booster compressor process area is calculated to be 1000 gpm based on two hoses. A separate calculation determines the minimum fire