Air Cooled Heat Exchanger Design Data by muhammadtayyab_87 is a document available to read on EtoBox.

This document contains the results of an air-cooled heat exchanger calculation for cooling a viscous fluid. The design requires cooling the fluid from 90 degrees C to 48 degrees C with a duty of 0.6 MW using ambient air at 38 degrees C. The calculation shows the heat exchanger will have 1 bay with 2 bundles of 123 tubes each that are 7.82 meters long. It will use 2 fans that are 11 feet wide and require 15 kW of power per fan. The bundle face area is 30.5 square meters and the total plot area is 40 square m