This passage discusses factors to consider when sizing cold-water pipe systems, including: 1) Demand flow rate, which is based on the types and number of fixtures as well as diversity factors. Constant use fixtures are added separately. 2) Velocity, which should be below 7 feet per second to avoid noise and below 4 feet per second to prevent erosion, depending on pipe material and water quality. 3) Pressure and available head for overcoming friction losses, which are calculated using charts and formulas