The document outlines ventilation requirements for rooms containing hazardous and flammable materials, referencing the UAE Fire and Life Safety Code - 2018. It specifies an extract air volume of 940 l/s based on 20 air changes and a make-up air volume of 799 l/s, which is 85% of the extract. The data is based on a room area of 36.0 m² and a height of 4.70 m.