Transformer Condition Monitoring Report by ravi142857 is a document available to read on EtoBox.
The document is a test report from Shanthala Power Limited summarizing condition monitoring tests performed on Power Transformer No. 2698/2. Key findings from the tests include: - Insulation resistance values between windings ranged from 3.0-4.5 GOhms and increased with time, indicating good insulation condition. - Tan delta values for windings and bushings were all below 0.01, within acceptable limits. - DC winding resistances varied appropriately with OLTC position, from 4207-3145 mOhms between phase