Can I read Unit 1&6 Island Mode Checklist on EtoBox?

Unit 1&6 Island Mode Checklist by Anonymous vcadX45TD7 is a document available to read on EtoBox.

What is Unit 1&6 Island Mode Checklist about?

Checklist for running unit 1&6 in island mode: 1) Check that specific transformers, ICT1, and ST1/ST4 are connected to 220KV Bus #1 and sectionalizer #1 is closed. 2) Check that generation from units 1&6 is balanced with loads on 220KV Bus #1 and ICT1 MVAR import/export is below 10 MVAR. 3) Do not couple buses 1&2, close bus coupler, or open sectionalizer #1. Inform utilities the system is now islanded and do not switch loads on or off.