About this document
Fan Coil Unit Resistance Overview by Adnan Attish is a document available to read on EtoBox.
This document provides details on 10 axial fans used for pressurizing staircases in a station. Each fan has a capacity of 7.5 kW and operates at 2900 RPM at 415V/3ph/50Hz. The fans come in pairs to service each staircase, with one unit on duty and the other on standby. The fans are designed to maintain a static pressure of 250 Pa and overcome a calculated external system resistance of 370 Pa.
- Author
- Adnan Attish
- Language
- EN