Opening book details…
Can I read D.G. Breakdown Incident Report on EtoBox?
D.G. Breakdown Incident Report by Talha Burny is a document available to read on EtoBox.
What is D.G. Breakdown Incident Report about?
1) Two generator sets supplying temporary power during cable replacement experienced issues. A 513KVA set associated with transformer 5SXF303-3 stopped due to an alternator problem, tripping frequently before being replaced. A 635KVA set associated with 5SXF304-2 stopped twice, first due to a damaged speed sensor and second time due to moisture in the speed sensor. 2) An investigation found the 513KVA set had issues with the alternator and automatic voltage regulator. The speed sensor was damaged on the 63
- Author
- Talha Burny
- Language
- EN