Minimum Size for Transformer Rooms by Dar Yiel Jose Reyes is a document available to read on EtoBox.

What is Minimum Size for Transformer Rooms about?

For a single unit distribution transformer room: - The minimum size shall be 6.25m x 4.25m x 4.0m for a 2000kVA transformer, and this size shall be maintained for future expansion. - A minimum 1.0m clearance shall be maintained from the inside walls to the transformer and equipment. - For multiple unit rooms, the size shall be negotiated with the relevant manager depending on supply requirements, with a minimum 1.0m clearance between units.