Electrical Load Schedule Example by Atty Atty is a document available to read on EtoBox.

This electrical load schedule document provides information on equipment power requirements. It recommends a 250kVA generator for the main operations and two booster pumps, with a total normal running load of 133kW and 82kVAr. With a 20% allowance for future expansion, the total load is estimated at 160kW, 99kVAr, and 188kVA. The peak load with intermittent and standby equipment is estimated at 192kW, 118kVAr, and 225kVA.