132kV Lightning Arrester Specifications by Guru Mishra is a document available to read on EtoBox.
This document provides technical specifications for surge arresters, including: 1. The arresters have a rated voltage of 120kV, maximum continuous operating voltage of 102kV, and nominal discharge current of 10kA. 2. Key specifications include a minimum discharge capability of 6kJ/kV, maximum residual voltages between 320-380kV, and short duration withstand of 100kA. 3. The arresters use approximately 40 zinc oxide discs in two units, with external insulation of hollow porcelain designed to withstand v