Wind Load Analysis for Wall Cladding by Jester Abucay is a document available to read on EtoBox.
This document summarizes the wind load analysis for an 18-foot wall according to the ASCE 7-05 code. It provides input data for the building and wall parameters and calculates the resulting wind pressures. The building is in Exposure Category C with a wind speed of 170 mph. The analysis uses the analytical procedure to determine zone pressures for the wall between -72.5 psf and 59.73 psf. It also notes the minimum design wind load shall not be less than 10 psf according to the code.