Fire Fighting System Design Calculations by Trang Ngo is a document available to read on EtoBox.

This document contains calculations for firefighting equipment for the Nutreco project. It calculates the required water flow rates for sprinklers and hoses, sizing the fire pump at 460 cubic meters per hour. It determines the necessary fire tank volume as 480 cubic meters. Pipe sizes and pump head are also calculated. The selected fire pump configuration includes one diesel pump and one electric pump, both rated at 460 cubic meters per hour and 110 meter head, plus a jockey pump rated at 46 cubic meters pe

Author
Trang Ngo
Language
EN