Metering CT Burden Calculation Guide by lalitendu jena is a document available to read on EtoBox.
This document provides calculations for sizing a metering current transformer (CT) with the following key details: - The CT will have a primary to secondary ratio of 200:1 with an accuracy class of 0.2 and an rated burden of 10VA. - Factors considered in the sizing include the ammeter and meter burden, lead resistance, and adding a 20% margin to the total burden of 1.43VA. - The recommended CT has a ratio of 200:1, accuracy class of 0.2, VA rating of 10VA, and an insulation factor less than or equal to