Can I read Transformer Selection and Cost Analysis on EtoBox?

Transformer Selection and Cost Analysis by N Ramakrishnan is a document available to read on EtoBox.

What is Transformer Selection and Cost Analysis about?

1. A 50MW power plant needs either a 50MVA ONAN transformer or a 40/50MVA ONAN/ONAF transformer. 2. The 40/50MVA transformer uses fans and can operate at higher loads, saving Rs. 786,298 per year in losses compared to the 50MVA transformer. 3. Ordering transformers with no negative tolerance on load losses could save Rs. 762,120 per year by choosing the 40/50MVA ONAN/ONAF transformer over the 50MVA ONAN transformer.