Opening book details…
Can I read Shell and Tube Heat Exchanger Analysis on EtoBox?
Shell and Tube Heat Exchanger Analysis by MRifqiWibiyanto is a document available to read on EtoBox.
What is Shell and Tube Heat Exchanger Analysis about?
1. The heat exchanger is used to cool 43200 lb/hr of 350 API distillate from 250 to 120°F using cooling water from 85 to 120°F. 2. The heat balance and log mean temperature difference calculations show a heat duty of 2920320 Btu/hr can be met. 3. The optimum outlet temperature of the cooling water is found to be 145°F for minimum annual cost considering annual operating hours, utility costs, and fixed capital charges.
- Author
- MRifqiWibiyanto
- Language
- EN