Chiller Load Profile and TES Design Summary by BalasundaramSrinivasaRajkumar is a document available to read on EtoBox.

1) The document outlines a load profile and plan to convert 2 water chillers to brine chillers to reduce peak load and utilize thermal energy storage. 2) The brine chillers will produce 624 tons during normal operation and 468 tons during ice making to charge storage tanks overnight. 3) A total of 11239 ton hours of storage will be produced to meet 18 hours of the peak load the next day without operating any chillers. 4) 80 storage tanks of 140 ton hours each are required to store the thermal energy for o