PARC Transformer Relay Settings Overview by Ritesh Bhatt is a document available to read on EtoBox.
What is PARC Transformer Relay Settings Overview about?
The document provides details for setting protection relays for a 750KVA transformer supplying a PARC substation. Key settings include: 1. For the PCC incomer relay, the transformer standby earth fault is set to 0.4A at 0.9s, and the PCC earth fault is set to 0.2A at 0.8s. Overcurrent is set to 0.875A at 0.5s. 2. For the 6.6kV feeder relay, phase overcurrent is set to 1.38A at 1s. High set phase overcurrent is set to 15.74A at 100ms. Earth fault is set to 1.2A