Diesel Generator NO2 Impact Assessment by estebandidochascon is a document available to read on EtoBox.
This document summarizes modeling conducted by the Air Quality Modeling and Assessment Unit (AQMAU) on the potential nitrogen dioxide (NO2) impacts of diesel generator arrays operating as backups for the National Grid. Modeling of three generator array sizes found that without control measures like tall stacks, hourly NO2 standards could be exceeded within 160m. With restrictions to 50 hours/year of operation, exceedances were possible within 150m. Meeting emission limits reduced this to 110m. Site-specific