Pusat Darah Wilayah Utara Sungai Petani by Jeghi is a document available to read on EtoBox.

The document discusses the selection of equipment for the chilled water system for a blood donation center in Northern Peninsular Malaysia. It determines requirements for a 375-ton water-cooled chiller system with one duty and one standby chiller. Based on the chiller capacity and design parameters, it sizes the chilled water pump at 750 gallons per minute, condenser water pump at 940 gallons per minute, and cooling tower at 600 heat rejection tons.