Can I read 30RB Chiller Service and Troubleshooting on EtoBox?
30RB Chiller Service and Troubleshooting by tezdhar18 is a document available to read on EtoBox.
What is 30RB Chiller Service and Troubleshooting about?
1. To control external pumps without the hydronic package, wire pump feedback contacts to J5C (CH 18) and set Configuration > OPTN > PUMP to 1. This will allow the chiller to control external pumps without alarms. 2. To enable automatic backup pump operation in a dual pump system, update to Smartload Version 1.09 or later. This will clear flow alarms and start the backup pump if the primary fails without a manual reset. 3. For dual chiller control, set the slave to CCN control and ensure both chillers ha