Cooling Tower Make Up Water Calculation by amdnazri.80 is a document available to read on EtoBox.

What is Cooling Tower Make Up Water Calculation about?

The document calculates the required make-up water for a cooling tower system with a chiller capacity of 235 RT. It determines the condenser water flow rate is approximately 590 imperial gallons per minute (igpm). It then calculates the make-up water percentage based on evaporation, drift, and blowdown losses to be 1.09% of the circulating water flow rate per hour. Taking a safety margin of 1.2%, the required make-up water is calculated to be 10,195 imperial gallons for 24 hours of operation. A proposed fib