About this document
Schneider I-Line II Busbar Specifications by sajeevi piumika is a document available to read on EtoBox.
This document provides specifications for an I-LINE II busbar trunking system manufactured by Schneider Electric. The key specifications are: 1) The busbar trunking must be sandwich construction and pass IEC 61439:2012 certification. 2) The system must be rated for 1000V operation and pass seismic and short circuit testing standards. 3) The housing must be constructed of steel/aluminum, coated in grey epoxy paint, and pass a 500-hour salt spray test. 4) The busbars must be high conductivity copper or
- Author
- sajeevi piumika
- Language
- EN