CESI Test Report: Neutral Earthing Resistor by deltastarconstruction.services is a document available to read on EtoBox.

The document reports the results of a temperature-rise test conducted on a single phase neutral earthing resistor according to ANSI/IEEE Std. 32-1972. The test subjected the resistor to a 1500A current for 10.1 seconds, raising its temperature from 9C ambient to an average of 508C at the end of the test. The resistor showed no damage after the test.