What is Insulation System Thermal Life Expectancy about?

The thermal life expectancy of an insulation system is generally designed to be approximately 20,000 to 25,000 hours when operated continuously at its maximum rated temperature. The "Rule of 10" approximates that reducing the total operating temperature by 10°C doubles the insulation life, while raising it by 10°C halves the life. Operating a generator with Class H insulation continuously at the Class F rating of 155°C can extend its thermal life from 20,000-25,000 hours to over 100,000 hours. Engineers may