Singarapet 110 KV Relay Calculations by R.EASWARAN is a document available to read on EtoBox.

- The document contains calculations for distance relay settings for the 110kV Samalpatty feeder line from Singarapet 110kV substation. - It details the line impedances, relay type, zone impedances and times. Zone 1 is set at 4.959Ω, Zone 2 at 6.423Ω, and Zone 3 at 13.132Ω. - Similar calculations are shown for the 110kV Arani-I feeder line with zone settings of Zone 1 at 10.836Ω, Zone 2 at 14.3Ω, and Zone 3 at 29.467Ω.