Wind Load and Footing Design Analysis by RAJENDRA PRASAD is a document available to read on EtoBox.
This document calculates wind loads on a barrier structure according to standard HA 66/95 and selects appropriate footing sizes. It summarizes: 1) Wind loads are calculated based on a gust speed of 50 m/s using factors from the standard like fetch, terrain, and structure type. Loads on posts range from 6.34 kN to 12.68 kN depending on location. 2) Moments on post footings are determined to range from 15.9 kN-m to 31.8 kN-m. Table C1 of the standard indicates an 850mm square footing is adequate except for
- Author
- RAJENDRA PRASAD
- Language
- EN