Can I read PLS-CADD Analysis for 44 kV Line on EtoBox?
PLS-CADD Analysis for 44 kV Line by JUAN SEBASTIAN GUERRERO PUERTO is a document available to read on EtoBox.
What is PLS-CADD Analysis for 44 kV Line about?
This document summarizes the steady-state thermal rating analysis of a 477 kcmil 26/7 Strands HAWK ACSR conductor for a transmission line from Mineros to 44 kV in Colombia. The analysis was performed using IEEE Standard 738-2006 and considers weather conditions of 28C air temperature, 0.61 m/s wind speed, and clear atmosphere. It finds a current rating of 633.946 Amps and conductor temperature of 80C under the specified conditions.