Can I read 132kV Depota GSS Multiple Tripping Report on EtoBox?
132kV Depota GSS Multiple Tripping Report by Protection Cell AEGCL is a document available to read on EtoBox.
What is 132kV Depota GSS Multiple Tripping Report about?
On April 7, 2024, a multiple tripping event occurred at the 132kV Depota GSS in Assam, resulting in a generation loss of 22.7MW and a load loss of 28MW, with an interruption duration of approximately 35 minutes. The event was triggered by a Y-B phase fault detected at the Ghoramari end, leading to the tripping of two major lines, while protection issues were identified at both ends of the affected lines. Remedial measures include rectifying phase sequence issues and updating protection settings to prevent f